進口水用可調(diào)式減壓閥
一、進口水用可調(diào)式減壓閥 產(chǎn)品概述
品牌:美國歐可OKE
進口水用可調(diào)式減壓閥,Water adjustable pressure reducing valve也叫水用調(diào)壓閥,主要由調(diào)節(jié)彈簧、膜片、活塞、閥座、閥瓣等零件組成,利用膜片直接傳感下游壓力驅(qū)動閥瓣,控制閥瓣開度完成減壓穩(wěn)壓功能的閥門。減壓閥上配有壓力調(diào)節(jié)按鈕,可根據(jù)用戶的閥后壓力需要值,對減壓閥進行各種高精度的壓力調(diào)節(jié)控制。
美國歐可OKE進口水用可調(diào)式減壓閥主要應(yīng)用在城市建筑、高層建筑的冷熱供水系統(tǒng)中,可取代常規(guī)分區(qū)水管,節(jié)省設(shè)備。也可在通常的冷熱水管網(wǎng)中,起減壓穩(wěn)壓作用。
主要特征:
◆結(jié)構(gòu)新穎合理、合理運用液壓原理控制論
◆工作平穩(wěn)可靠、大流量通行
◆閥瓣快開慢閉、無水錘沖擊(關(guān)閉時間可調(diào))
◆減穩(wěn)壓精度高、調(diào)節(jié)范圍大
◆密封性能好、使用壽命時間長
◆安裝、調(diào)壓、維修方便
二、進口水用可調(diào)式減壓閥 技術(shù)參數(shù)及性能
型號 OKE
公稱壓力(Mpa) 1.0 1.6 2.5
殼體試驗壓力(Mpa)* 1.5 2.4 3.75
密封試驗壓力(Mpa) 1.0 1.6 2.5
進口壓力(Mpa) 1.0 1.6 2.5
出口壓力范圍(Mpa) 0.2-0.8 0.2-1.0 0.4-1.6
壓力特性偏差(Mpa)△P2P GB12244-1989,API690,ANSI
流量特性偏差(Mpa)P2G GB12244-1989, API690,ANSI
滲漏量 0
工作溫度 0℃-80℃
三、進口水用可調(diào)式減壓閥 額定流量系數(shù)
DN 15 20 25 32 40 50 65 80 100 125 150 200 250 300 350 400 500
Cv 1 2.5 4 6.5 9 16 25 36 64 100 140 250 400 570 780 1020 1500
四、進口水用可調(diào)式減壓閥 零件材料
零件名稱 零件材料
閥體 閥蓋 底蓋 WCB
閥座 2Cr13
閥瓣 2Cr13
閥桿 2Cr13
缸套 2Cr13/25(鍍硬鉻)
活塞 2Cr13
O型圈 丁腈橡膠
密封圈 丁腈橡膠
膜片 夾織物丁腈橡膠
調(diào)節(jié)彈簧 60Si2Mn
五、進口水用可調(diào)式減壓閥 部分業(yè)績
三亞文華東方酒店、香格里拉臺南遠東國際大飯店、波士頓文華東方酒店、布拉格凱賓斯基、迪拜塔、臺北101大廈、上海金融中心、香港貿(mào)易廣場蒙特里凱悅度假村、曼谷香格里拉大酒店、波爾托羅曰凱賓斯基酒店、巴黎瑪?shù)氯R娜凱悅酒店、布達佩斯卡爾維努斯凱賓斯基酒店
六、進口水用可調(diào)式減壓閥 安裝注意事項
1.為了操作和維護方便,該閥一般直立安裝在水平管道上。
2.減壓閥安裝必須嚴(yán)格按照閥體上的箭頭方向保持和流體流動方 減壓閥
向一致。如果水質(zhì)不清潔含有一些雜質(zhì),必須在減壓閥的上游進水口安裝過濾器
3.為了防止閥后壓力超壓,應(yīng)在離閥出口不少于4M處安裝一個減壓閥。
4.減壓閥在管道中起到一定的止回作用,為了防止水錘的危害,也可安裝小的膨脹水箱,防止損壞管道和閥門,過濾器必須安裝在減壓閥的進水管前,而膨脹水箱必須安裝在減壓閥出水管后!
Adjustable pressure reducing valve for imported water
1. Adjustable pressure reducing valve for imported water Product Overview
Brand: US Ouke OKE
Water adjustable pressure reducing valve is also called water pressure regulating valve. It is mainly composed of adjusting spring, diaphragm, piston, valve seat and valve disc. It uses diaphragm to directly sense downstream pressure drive. The valve flap controls the valve opening to complete the decompression and pressure regulation function. The pressure reducing valve is equipped with a pressure adjustment button, which can perform various high-precision pressure adjustment control on the pressure reducing valve according to the user's post-valve pressure demand value.
The US Ou Ke OKE imported water adjustable pressure reducing valve is mainly used in the urban and high-rise building's hot and cold water supply system, which can replace the conventional partition water pipe and save equipment. It can also be used in the normal hot and cold water pipe network to reduce the pressure.
Main features:
◆The structure is novel and reasonable, and the hydraulic principle control theory is rationally applied.
◆Stable and reliable work, large traffic
◆Valve opening and closing slowly, no hammer impact (closed time adjustable)
◆High voltage regulation and high adjustment range
◆Good sealing performance and long service life
◆ Easy installation, pressure regulation and maintenance
2. Adjustable pressure reducing valve for imported water Technical parameters and performance
Model OKE
Nominal pressure (Mpa) 1.0 1.6 2.5
Shell test pressure (Mpa)* 1.5 2.4 3.75
Sealing test pressure (Mpa) 1.0 1.6 2.5
Maximum import pressure (Mpa) 1.0 1.6 2.5
Export pressure range (Mpa) 0.2-0.8 0.2-1.0 0.4-1.6
Pressure characteristic deviation (Mpa) △ P2P GB12244-1989, API690, ANSI
Flow characteristic deviation (Mpa) P2G GB12244-1989, API690, ANSI
Leakage 0
Working temperature 0°C-80°C
3. Adjustable pressure reducing valve for imported water
DN 15 20 25 32 40 50 65 80 100 125 150 200 250 300 350 400 500
Cv 1 2.5 4 6.5 9 16 25 36 64 100 140 250 400 570 780
4. Adjustable pressure reducing valve for imported water
Part Name Part Material
Body bonnet bottom cover WCB
Seat 2Cr13
Disc 2Cr13
Stem 2Cr13
Cylinder liner 2Cr13/25 (hard chrome plating)
Piston 2Cr13
O-ring nitrile rubber
Sealing ring
Diaphragm clip fabric nitrile rubber
Adjustment spring 60Si2Mn
V. Adjustable pressure reducing valve for imported water
Mandarin Oriental, Sanya, Shangri-La's Far Eastern Plaza Hotel, Boston, Mandarin Oriental, Boston Kempinski, Burj Khalifa, Taipei 101, Shanghai World Financial Center, Hyatt Regency Hong Kong Global Commerce Plaza, Shangri-La, Bangkok Hotel, Kempinski Hotel Portoro?, Hyatt Regency Paris Madeleine, Kempinski Hotel Calvinus Budapest
6. Adjustable pressure reducing valve for imported water Installation precautions
1. For ease of operation and maintenance, the valve is generally mounted upright on a horizontal pipe.
2. The pressure reducing valve must be installed in strict accordance with the direction of the arrow on the valve body and the fluid flow side pressure reducing valve
Consistent. If the water quality is not clean and contains some impurities, the filter must be installed at the upstream inlet of the pressure reducing valve.
3. In order to prevent post-valve pressure overpressure, a pressure reducing valve should be installed at not less than 4M from the valve outlet.
4. The pressure reducing valve plays a certain role in the pipeline. In order to prevent the damage of the water hammer, a small expansion tank can also be installed to prevent damage to the pipeline and the valve. The filter must be installed in front of the inlet pipe of the pressure reducing valve. The expansion tank must be installed after the pressure relief valve outlet!